Industrial Water Source Heat pumps TWW EVI HeavyDuty

High-efficiency heat pump consisting of multiple modules of separate heat pumps. Each module contains one short closed refrigerant circuit with a pair of quiet Scroll compressors and robust stainless steel plate heat exchangers. Applications range from heating, cooling and domestic hot water heating of office or multi-functional buildings to cascading applications in industrial applications.
Use for demanding industrial applications. By combining the most suitable performance and application variants of heat pump modules, it is possible to tailor-make the complete system required. Each module is refrigeration, hydraulically and electrically isolated with a separate controller. The connection of the modules is cascaded, whereby each single controller can take over the function of the cascade master.
As a primary source, thermal energy from underground water at a depth of between 12 and 30 metres is used. A submersible pump delivers the groundwater to the heat pump and, depending on the quality and chemical composition, the heat from the groundwater is extracted either directly in the heat pump or through a separating heat exchanger with an intermediate circuit and antifreeze. The heat pump then raises this temperature to a usable temperature for heating or hot water.

Heat pump type: TWW HeavyDuty 240 EVI HD 360 EVI HD 480 EVI HD 600 EVI HD
Product sheet
Article nr. WAHDW2XE WAHDW3XE WAHDW4XE WAHDW5XE
Heating capacity [ kW ] EN 14511
W10 / W35 (max) 247.9
(62.0 ~ 247.9)
371.8
(62.0 ~ 371.8)
495.8
(62.0 ~ 495.8)
619.7
(62.0 ~ 619.7)
W10 / W35 (min) 62.0
(62.0 ~ 247.9)
62.0
(62.0 ~ 371.8)
62.0
(62.0 ~ 495.8)
62.0
(62.0 ~ 619.7)
W10 / W34 248.0
(62.0 ~ 248.0)
372.0
(62.0 ~ 372.0)
496.0
(62.0 ~ 496.0)
619.9
(62.0 ~ 619.9)
W10 / 55 (max) 246.7
(61.7 ~ 246.7)
370.1
(61.7 ~ 370.1)
493.4
(61.7 ~ 493.4)
616.8
(61.7 ~ 616.8)
W10 / W55 (min) 61.7
(61.7 ~ 246.7)
61.7
(61.7 ~ 370.1)
61.7
(61.7 ~ 493.4)
61.7
(61.7 ~ 616.8)
W10 / W52 249.3 (62.3 ~ 249.3) 373.9 (62.3 ~ 373.9) 498.6 (62.3 ~ 498.6) 623.2 (62.3 ~ 623.2)
Energy Efficiency Parameters and Performance ErP [ middle temperature region ]
Rated nominal heating capacity P rated [ kW ] 247.9 371.8 495.8 619.7
Energy class A+++ A+++ A+++ A++
SCOP 5.62 4.34 3.79 3.51
Seasonal energy efficiency η [ % ] 224.7 173.6 151.7 140.3
Bivalent point [ ºC ] -10 -10 -10 -10
Parameter of heat sink
Maximal flow temperature [ ºC ] 65 65 65 65
Minimal flow temperature [ ºC ] 25 25 25 25
Flow nominal [ m3/h ] [@35/30] 10.68 ~ 42.73 10.70 ~ 64.18 10.70 ~ 85.63 10.71 ~ 107
Pressure drop [ kPa ] [@35/30] 2 x 20 3 x 20 4 x 20 5 x 20
Nominal ∆T [ K ] [@W35°C] 5 5 5 5
Nominal ∆T [ K ] [@W55°C] 8 8 8 8
Nominal ∆T [ K ] [@W65°C] 10 10 10 10
Connection port size [ " ] 2 x VIC 2.1/2" 3 x VIC 2.1/2" 4 x VIC 2.1/2" 5 x VIC 2.1/2"
Parameter of low temperature heat source
Minimal source temperature [ ºC ] -10 (7) -10 (7) -10 (7) -10 (7)
Maximal source temperature [ ºC ] 30 30 30 30
Flow source nominal [ m3/h ] 11.05 ~ 44.20 11.05 ~ 66.32 11.05 ~ 88.42 12.00 ~ 120
Pressure drop source [ kPa ] 2 x 20 3 x 20 4 x 20 5 x 20
Nominal ∆T source [ K ] 4 4 4 4
Connection port size source [ " ] 2 x VIC 2.1/2 3 x VIC 2.1/2 4 x VIC 2.1/2 5 x VIC 2.1/2
Electrical parameters
Voltage [ V ] 3~ 400/50 3~ 400/50 3~ 400/50 3~ 400/50
Safety protection [ A ] C160 C240 C300 C400
Current - nominal [ A ] 94.12 141.18 188.24 235.30
Current - maximal [ A ] 149.60 224.40 299.20 374.00
Current - Start [ A ] 57.2 57.2 57.2 57.2
Softstart 4 x MCD 201 6 x MCD 201 8 x MCD 201 10 x MCD 201
Sound information
Sound power - indoor Lw [ dB(A) ] 69 72 76 77
Sound power - outdoor Lw [ dB(A) ]
Sound pressure Lp in 1 meter [ dB(A) ] 61 64 68 69
Sound pressure Lp in 5 meter [ dB(A) ] 47 50 54 55
Sound pressure Lp in 10 meter [ dB(A) ] 41 44 48 49
Sound pressure Lp in 15 meter [ dB(A) ] 38 41 44 46
20 + 11 =


Technical Sales & Support
West Europe
WAMAK Italia Sas
sales@wamakitalia.it

Central/East Europe
WAMAK s.r.o. Slovakia
sales@wamak.eu